Concrete Mix Design M-60

CONCRETE MIX DESIGN (GRADE M60)


(a) DESIGN STIPULATION:-
Target strength = 60Mpa
Max size of aggregate used = 12.5 mm
Specific gravity of cement = 3.15
Specific gravity of fine aggregate (F.A) = 2.6
Specific gravity of Coarse aggregate (C.A) = 2.64
Dry Rodded Bulk Density of fine aggregate = 1726 Kg/m3
Dry Rodded Bulk Density of coarse aggregate = 1638 Kg/m3

Step-1
Calculation for weight of Coarse Aggregate:
From ACI 211.4R Table 4.3.3 Fractional volume of oven dry Rodded C.A for 12.5mm size aggregate is 0.68m3
Weight of C.A = 0.68*1638 = 1108.13 Kg/m3

Step-2
Calculation for Quantity of Water:
From ACI 211.4R Table 4.3.4
Assuming Slump as 50 to 75mm and for C.A size 12.5 mm the Mixing water = 148 ml
Void content of FA for this mixing water = 35%
Void content of FA (V)
V = {1-(Dry Rodded unit wt / specific gravity of FA*1000)}*100
= [1-(1726/2.6*1000)]*100
= 34.62%

Adjustment in mixing water = (V-35)* 4.55
= (34.62 – 35)*4.55
= -1.725 ml
Total water required = 148 + (-1.725) = 146.28 ml
Step-3
Calculation for weight of cement
From ACI 211.4R Table 4.3.5(b)
Take W / C ratio = 0.29
Weight of cement = 146.28 / 0.29 = 504.21 kg/m3

Advertisements

Step-4
Calculation for weight of Fine Aggregate:

Cement = 504.21 / 3.15*1000= 0.1616
Water = 146.28 / 1*1000= 0.1462
CA = 1108.13 / 3*1000= 0.3690
Entrapped Air = 2 / 100= 0.020
Total = 0.7376m3
Volume of Fine Aggregate= 1-0.7376
Weight of Fine Aggregate= 0.2624*2.6*1000= 683.24 kg/m3

Step-5
Super plasticizer:
For 0.8% = (0.8 / 100)*583.53 = 4.668 ml

Step-6
Correction for water:
Weight of water (For 0.8%) =146.28 – 4.668 =141.61 kg/m3

Requirement of materials per Cubic meter
Cement = 504.21 Kg/m3
Fine Aggregate = 683.24 Kg/m3
Coarse Aggregate = 1108.13 Kg/m3
Water = 141.61 Kg/ m3
Super plasticizers = 4.6681 / m3

So the final ratio becomes
Cement : Fine agg (kg/m3) : Coarse agg (kg/m3) : Water (l/m3): Superplasticizer (l/m3)

1: 1.35 :2.19 :0.29 :0.8

Advertisements

This concrete mix design has been submitted to us by Natarajan. We are thankful to him for this valuable contribution.

Share this post

Kanwarjot Singh

Kanwarjot Singh is the founder of Civil Engineering Portal, a leading civil engineering website which has been awarded as the best online publication by CIDC. He did his BE civil from Thapar University, Patiala and has been working on this website with his team of Civil Engineers.

If you have a query, you can ask a question here.

163 comments on "Concrete Mix Design M-60"

Kaushal Kishore says:

As per IS:456-2000, OPCement shall not be more than 450 kg/m3.
Normally mixes of M-60 are designed with less than 450 kg/m3 of OPCement.
Please see this Cement And Water Saving With Water Reducers

TUSHAR MUNDADA says:

Which is the maximum grade of concrete ??

Ranganath says:

Do we have mix design for SCC as per Indian standards

Frana says:

May I please have a concrete mix design of strength 60 Mos using cement of 42,5N using the C&CI method, it is for a project, please help.

Anju Chandran says:

Sir
Please give the mix design for M60 using IS Code

salmanfarish says:

do u having the mix design for those u asked above grade

girish says:

sir ;
maximum cement for design mix 450 kg/m3, then how you take above 500 kg??

Hassan Shafeeq says:

Dear Sir,

Thanks for your efforts in concrete mix design. But I think using more than 500 Kg/m3 of Cement will give us a lot of problems starting from thermal stress which will cause a lot of problems in concrete….

Rajendra Mistry says:

We need exact calculation and Apx cost for RCC M- 60 / 23° C temperature….pl help

Mangesh ghodake says:

Do you having mix design For M60 grade concrete by using fly ash and silica fume.

do you have mix desgin for M55 & M60 by using silica fume and fly ash says:

plz mail excel or pdf if you have any one who would like to help me i need this for my project

Muhammad Khalid Khan says:

R/Sir, send me 60 mpa, 50 mpa concrete Charictestic detail such as quantity of cement ,sand, water, water cement ratio, temprature. chemical add

Leave a Reply

Your email address will not be published. Required fields are marked *

Ask a question