Following table shows the M-30 Mix Designs as per IS-10262-2009, hope this helps all civil engineers here
M-30 CONCRETE MIX DESIGN |
||
As per IS 10262-2009 & MORT&H |
||
A-1 |
Stipulations for Proportioning | |
1 |
Grade Designation | M30 |
2 |
Type of Cement | OPC 53 grade confirming to IS-12269-1987 |
3 |
Maximum Nominal Aggregate Size | 20 mm |
4 |
Minimum Cement Content (MORT&H 1700-3 A) | 310 kg/m3 |
5 |
Maximum Water Cement Ratio (MORT&H 1700-3 A) | 0.45 |
6 |
Workability (MORT&H 1700-4) | 50-75 mm (Slump) |
7 |
Exposure Condition | Normal |
8 |
Degree of Supervision | Good |
9 |
Type of Aggregate | Crushed Angular Aggregate |
10 |
Maximum Cement Content (MORT&H Cl. 1703.2) | 540 kg/m3 |
11 |
Chemical Admixture Type | Superplasticiser Confirming to IS-9103 |
A-2 |
Test Data for Materials | |
1 |
Cement Used | Coromandal King OPC 53 grade |
2 |
Sp. Gravity of Cement | 3.15 |
3 |
Sp. Gravity of Water | 1.00 |
4 |
Chemical Admixture | BASF Chemicals Company |
5 |
Sp. Gravity of 20 mm Aggregate | 2.884 |
6 |
Sp. Gravity of 10 mm Aggregate | 2.878 |
7 |
Sp. Gravity of Sand | 2.605 |
8 |
Water Absorption of 20 mm Aggregate | 0.97% |
9 |
Water Absorption of 10 mm Aggregate | 0.83% |
10 |
Water Absorption of Sand | 1.23% |
11 |
Free (Surface) Moisture of 20 mm Aggregate | nil |
12 |
Free (Surface) Moisture of 10 mm Aggregate | nil |
13 |
Free (Surface) Moisture of Sand | nil |
14 |
Sieve Analysis of Individual Coarse Aggregates | Separate Analysis Done |
15 |
Sieve Analysis of Combined Coarse Aggregates | Separate Analysis Done |
15 |
Sp. Gravity of Combined Coarse Aggregates | 2.882 |
16 |
Sieve Analysis of Fine Aggregates | Separate Analysis Done |
A-3 |
Target Strength for Mix Proportioning | |
1 |
Target Mean Strength (MORT&H 1700-5) | 42N/mm2 |
2 |
Characteristic Strength @ 28 days | 30N/mm2 |
A-4 |
Selection of Water Cement Ratio | |
1 |
Maximum Water Cement Ratio (MORT&H 1700-3 A) | 0.45 |
2 |
Adopted Water Cement Ratio | 0.42 |
A-5 |
Selection of Water Content | |
1 |
Maximum Water content (10262-table-2) | 186 Lit. |
2 |
Estimated Water content for 50-75 mm Slump | 160 Lit. |
3 |
Superplasticiser used | 0.5 % by wt. of cement |
A-6 |
Calculation of Cement Content | |
1 |
Water Cement Ratio | 0.42 |
2 |
Cement Content (160/0.42) | 380 kg/m3 |
|
Which is greater then 310 kg/m3 | |
A-7 |
Proportion of Volume of Coarse Aggregate & Fine Aggregate Content | |
1 |
Vol. of C.A. as per table 3 of IS 10262 | 62.00% |
2 |
Adopted Vol. of Coarse Aggregate | 62.00% |
|
Adopted Vol. of Fine Aggregate ( 1-0.62) | 38.00% |
A-8 |
Mix Calculations | |
1 |
Volume of Concrete in m3 | 1.00 |
2 |
Volume of Cement in m3 | 0.12 |
|
(Mass of Cement) / (Sp. Gravity of Cement)x1000 | |
3 |
Volume of Water in m3 | 0.160 |
|
(Mass of Water) / (Sp. Gravity of Water)x1000 | |
4 |
Volume of Admixture @ 0.5% in m3 | 0.00160 |
|
(Mass of Admixture)/(Sp. Gravity of Admixture)x1000 | |
5 |
Volume of All in Aggregate in m3 | 0.718 |
|
Sr. no. 1 – (Sr. no. 2+3+4) | |
6 |
Volume of Coarse Aggregate in m3 | 0.445 |
|
Sr. no. 5 x 0.62 | |
7 |
Volume of Fine Aggregate in m3 | 0.273 |
|
Sr. no. 5 x 0.38 | |
A-9 |
Mix Proportions for One Cum of Concrete (SSD Condition) | |
1 |
Mass of Cement in kg/m3 | 380 |
2 |
Mass of Water in kg/m3 | 160 |
3 |
Mass of Fine Aggregate in kg/m3 | 711 |
4 |
Mass of Coarse Aggregate in kg/m3 | 1283 |
|
Mass of 20 mm in kg/m3 | 924 |
|
Mass of 10 mm in kg/m3 | 359 |
5 |
Mass of Admixture in kg/m3 | 1.90 |
6 |
Water Cement Ratio | 0.42 |
We are thankful to Er. Raj M. Khan for sharing this information with us on engineeringcivil.com. We hope this would be of great significance to civil engineers.
If you have a query, you can ask a question here.
thanks for your guidance about mix design sir…….
Dear sir,
If i use the specific gravity -dry, for the calculations of mix design, is there any problem for the presentation?
No, You can not use the dry specific Gravity, because you have to maintain W/C ratio & After that the moisture correction is to be made. else the desired slump can not be achieved.
which admixture will used in M30 grade concrete ,give ex.
please give description about unit weight of m30
just add the concrete ingredients of m-30
water =173.23 kg cement= 455.87kg fine aggregate (specific gravity2.67 =442.27 kg
coarsse aggregate specific gravity (2.92) = 1405.69 kg
unit wt of m30 after 28days curing is = 2650kg /cum in lab condition it may be deffer at site
thanks for every one helping each other
its my pleasure
Can you plz help me with m30 mix ratio in litres.it would be very helpful of you. Ithank you
Very thankful to you sir
sir for making m-30 or m40 class paver which machine i purchase technically.thanks
dear, sir can u write me what are the ratio i used (cement, sand, stone dust,water or any chemical for making of solid bricks) which is harden and can be used for construction of building. i newly start production of cement solid brick for rural people which is cheaper then clay brick thankin you
Can you plz help me with m30 mix ratio in kg.it would be very helpful of you. Ithank you
Dear sir,
If i use the specific gravity -dry, for the calculations of mix design, is there any problem for the presentation?
for the example that you have solved for m30 what’s the mix ratio sir
what is mix ratio for m30
am gettin 41.5 as strength at th7 day for m30 amd opc 53. is it correct
can anyone tel me mix proportion for M30 in terms of ghamela ??? like at site i used normal concrete mixer . so wat do i need to tell to labour to pour in the materials
This is very necessary for all civil engineers. Thanks to all.
How can we calculate the Mix design for M-30 C.C keeping cement content constant ?
can design mix concrete be converted into nominal mix concrete at work site for concrete grade more than M25 and above.
can i suggest some clarity and improvement?
Dear sir can U write me the mixer machine mix m-30 site. pl. write me Box size. Thanking you
Thanks for your information regards mix design of m30